Rigid installation cable halogen free, MMJ EQQ Literex
INSTALLATION CABLE EQQ LITEREX 4G2,5 DCA
With registration you can access the Würth Elektro online shop selection.
EQQ LiteRex halogen-free installation cable. Finnish next generation fully UV protected halogen-free installation cable. Suited for indoor and outdoor stationary installations with no need for separate UV protection in the jacket or conductor insulation. LiteRex is CPR Dca-s2, d2, and a2 tested and certified, making it suitable for most applications. LiteRex installation cables are safe and environmentally friendly. All plastic materials used in the cable are halogen-free thermoplastics, and fully recyclable. In the event of a fire, a halogen-free cable releases noticeably smaller amounts of toxic and corrosive gas than traditional PVC cables. It is fire retardant, and its low smoke production facilitates evacuation. LiteRex is specially designed with the installer in mind. It is flexible, retains its shape well, and is extremely easy to strip. The cable is well suited for Nordic applications and can be installed at temperatures as cold as –15 ⁰C. This product is designed and made in Finland.
Datasheets(X)
Conductor material | Copper |
Conductor surface | Bare |
Nominal cross section conductor | 2.5 mm² |
AWG size | 14 |
Nominal cross section conductor (AWG) | 2.08 kcmil |
Diameter conductor | 1.74 mm |
Conductor category | Class 1 = solid |
Conductor resistance at 20 °C | 7.41 Ohm/km |
Number of cores | 4 |
Twisted cores | Yes |
Material core insulation | Polyolefin |
Specification core insulation | Polyethylene (PE) |
Core identification according to HD 308 S2 | Yes |
Identification/coding colour core | Other |
Core identification | Colour |
Core colour | Several |
With protective conductor | Yes |
Max. conductor temperature | 70 °C |
Screen | No |
Drain wire | No |
Protective barrier | None |
Armouring/reinforcement | None |
Material outer sheath | Polyolefin |
Specification material outer sheath | Other |
Colour outer sheath | White |
Cable geometry | Round |
Reaction-to-fire according to EN 13501-6: Class | Dca |
Reaction-to-fire according to EN 13501-6: Smoke production | s2 |
Reaction-to-fire according to EN 13501-6: Flaming droplets/particles | d2 |
Reaction-to-fire according to EN 13501-6: Acidity | a2 |
Halogen free according to EN 60754-1/2 | Yes |
Flame retardant | According to IEC/EN 60332-3-24 |
Low temperature resistant according to EN 60811-504+505+506 | Yes |
Oil resistant according to EN IEC 60811-404 | No |
Insulation integrity | None |
Outer diameter approx. | 11 mm |
Min. permitted bending radius, stationary application/permanent installation | 33 mm |
Permitted cable outer temperature during assembling/handling | -15-+70 °C |
Permitted cable outer temperature after assembling without vibration | -15-+70 °C |
Nominal voltage U0 | 300 V |
Nominal voltage U | 500 V |
Circuit integrity | None |
Shape of conductor | Round |
Suitable as installation cable | Yes |
Certified for shipboard application | No |
Suitable as medium-voltage cable | No |
Suitable as high-voltage cable | No |
Certified as airport lighting cable | No |
E-number Finland | 0456566 |