Residual current circuit breaker +ReStart 90ReStart PRO
RCB 2-P. 40A 30mA GW90912B
GEWISS
Art.-no. WS3202694
EAN 8034035040511
With registration you can access the Würth Elektro online shop selection.
ReStart Autotest automates the testing of the residual current circuit breaker. When the RCCB trips, ReStart performs an insulation check before automatic reclosing. If the fault is caused by ground leakage current, ReStart will not reset the breaker but will continue monitoring the circuit at 2-minute intervals and reclose it only when the electrical system is safe.
During this time, the integrated and configurable auxiliary contact changes state to indicate that automatic reclosing has not been carried out. This improves system monitoring and enables the status signal to be used, for example, in control logic or remote monitoring applications.
NOTE. The automatic test function tests the RCCB every 28 days without interrupting the power supply, thereby maintaining the long-term performance of the residual current protection device.
Datasheets(X)
![]() | |
Number of poles | 2 |
Rated voltage | 230 V |
Rated current | 40 A |
Rated fault current | 0.03 A |
Mounting method | DIN rail |
Leakage current type | A |
Selective protection | No |
Short-time delayed tripping | Yes |
Surge current capacity | 3 kA |
Additional equipment integrated | Selftest, automatic reclosing and auxiliary switch |
Additional equipment attached at delivery | Monitoring unit with automatic reclosing |
Rated switch current auxiliary device | 40 A |
Rated voltage auxiliary device | 230 V |
Control voltage type auxiliary equipment | AC |
Degree of protection (IP) | IP20 |
Width in number of modular spacings | 7 |
Built-in depth | 72 mm |
Construction size according to DIN 43880 | 2 |
E-number Finland | 3202694 |
Brand | GEWISS |