Residual current circuit breaker with overcurrent protection AFA Hager
RCBO AFA940H 300MA A/2X40A C-CURVE
HAGER
With registration you can access the Würth Elektro online shop selection.
Residual current circuit breaker with overcurrent protection with 300mA trip sensitivity and type A function. The device is in accordance with DIN VDE 0664 part 20 / EN 61009‑1 and DIN VDE 0664 part 21 / EN 61009‑2‑1. Contact protection according to DIN VDE 0660 part 514.
The product has dual connectors for busbar and conductor connection and a blue test button on the front panel and a residual current fault indicator. Replacing and adding a device to a power rail installation is easy with the DIN rail mount. Equipped with a hinged marking window and compatible with retrofittable additional modules.
24 month warranty
Datasheets(X)
Number of poles (total) | 2 |
Rated voltage | 240 V |
Rated current | 40 A |
Rated fault current | 0.3 A |
Leakage current type | A |
Current limiting class | 3 |
Rated short-circuit breaking capacity according to IEC 60947-2 | 10 kA |
Voltage type | AC |
Frequency | 50 Hz |
Release characteristic | C |
Overvoltage category | 3 |
Pollution degree | 2 |
Width in number of modular spacings | 2 |
Built-in depth | 68 mm |
Degree of protection (IP) | IP20 |
E-number Finland | 3260759 |
Brand | HAGER |